Let, maximum flux density (Bm) =1.2 wb/m2
current density (δ) =2.3A/mm2
Let, k=0.45 for three phase core type distribution transformer
Overall Dimension
Core Design:
Voltage per turn (Et) = K√Q= 0.45*√150= 5.5 V
Voltage per turn (Et) = 4.44*f*Bm*Ai
Ai = 5.5/(4.44*50*1.1) = 20.6*103 mm2
Using a cruciform core, Ai = 0.56*d2
Diameter of circumscribing circle (d) = √((20.6*〖10〗^3)/0.56) = 192.2 mm
Length of largest core stamping (a) =0.85*d = 0.85*191.8 = 163.37 mm
Length of second largest core stamping (b) =0.53*d = 0.53*191.8
= 101.87 mm
Window Dimension:
Window space factor (kw) = 10/(30+kv) =10/(30+33/√3) = 0.2
Output of transformer (Q) = 3.33*f*Bm*Ai*kw*Aw* δ*10-3 KVA
Aw =150/(3.33*50*1.2*20.6*〖10〗^(-3)*0.2*2.3*〖10〗^6*〖10〗^(-3) ) = 79.22*103 mm2
Taking the ratio of height to width of window as 3,
Hw* Ww = 79.22*103
3Ww2 =79.22*103
Ww = 160.5mm
Hw = 487.5 mm
Distance between adjacent core centres (D) = Ww + d =160.5 + = 333.321 mm
Yoke Design
The area of yoke is taken as 1.2 times that of limb.
∴ Flux density in yoke = 1.2/1.2 =1.0 wb/m2
Net area of yoke = 1.2*20.6*103 = 24.72*103 mm2
Gross area of yoke = (24.72*〖10〗^3)/0.9 = 27.47*103 mm2
Taking the section of the yoke as rectangle.
Depth of yoke (Dy) = a = 163.37 mm
Height of yoke (Hy) = (27.467*〖10〗^3)/163.37 =168.13 mm
Overall Dimension of frame:
Height of frame (H) = Hw + 2*Hy = 823.76mm
Width of frame (W) = 2*D + a = 911.17mm
Depth of frame (Dy) = a = 163.37 mm
Lower Voltage side winding:
Secondary line voltage = 11000 v ;
connection = delta
Secondary phase voltage = 11000 v
Number of turns per phase (Ts) = 11000/5.5 = 2000
Secondary phase current (Is) = (150*〖10〗^3)/(3*11000) = 4.54 A
LV winding line current = 7.86 A
A current density of 2.3 A/mm2 is used.
Area of secondary conductor (as) = (4.54 )/2.31 = 1.978 mm2
Diameter of bare conductor, d=√(4/π*1.978) =1.58mm
From table 23.1 (IS:1897-1962),
using a bare conductor of diameter of 1.6 mm and insulated diameter of 1.775 mm
Modified area of conductor=π/4*1.62 =2.01mm2
.∙.Actual value of current density δp=4.54/2.01=2.26 A/mm2
Using 8 coils of 250 turns each
Voltage per turn=11000/8=1375 V
which is within the limit.
Using normal coil of 250 turns
Taking 10 layers per coil, turn per coil =250/10 =25
Maximum voltage between layers = 2*25*5.5 =275 V, which is below the allowable limit.
Axial depth of one coil ofL.V winding = 25*1.775 = 44.375 mm
The spacers used between adjacent coils are 5 mm in height
.
Axial length of LV winding ,Lcs=8*44.375 + 8*5=395 mm
The height of window is 487.5 mm. This leaves a clearance of (487.5 – 395) = 46.25mm on each side of the winding.
using 0.5 mm pressboard cylinders between layers,
Radial depth of L.v winding (bs) = number of layers * radial depth of conductor + insulation between layers
= 10*1.775 + 9*0.5 = 22.25 mm
Diameter of circumscribing circle (d) = 192.2 mm
Using pressboard wraps 1.5 mm thick as insulation between l.v winding and core.
Inside diameter of l.v winding = 192.2+2*1.5 = 195.2 mm
Outside diameter of l.v winding = 195.2+2*22.25 = 240.2 mm
Higher voltage side winding
Primary line voltage=33000 v
connection type: Star
Primary phase voltage=19052 v
Number of turn per phase, Tp=2000* 19052/11000 = 3464
Using 13 coils,
Voltage per coil=19052/13=1465.53 V , which is within the limit.
Turns per coil=( 3464)/13=266.46
Using 12 coils of 250 turns each and a reinforced coil of 464 turns,
Total hv turn Tp=12*250+464=3464
Taking 10 layers per coil, turn per coil =280/10 =25
maximum voltage between layer= 2*25*5.5=275 v
HV winding phase current=150* 1000/(3*19052) =2.624 A
Taking current density as 2.3A/mm2 ,
Area of high voltage conductor ,as=2.624/2.3=1.14 mm2
Diameter of bare conductor, d=√(4/π*1.14) =1.20mm
From the table(BIS: 3454-1966),
nearest standard conductor size has
Bare diameter= 1.25mm
Insulated diameter= 1.45 mm with fine covering
Modified area of conductor=π/4*1.52 =1.22 mm2
.∙.Actual value of current density δp=2.624/1.22=2.13 A/mm2
Axial depth of 1 coil=25*1.45=36.25mm
The spacers used between adjacent coils are 3 mm in height.
Axial length of HV winding ,Lcp=12*36.25+12*3=471 mm
Height of window is 487.5mm,
Space left between winding and window is 487.5-471=16.5mm
Clearance left on each side=8.25mm which is within the limit for 33 Kv.
Let the insulation between the layer is 0.5mm thick paper.
∴ The radial depth of HV coil, bP=10*1.45+0.5*9=19mm
The thickness of insulation between HV and LV =5+0.9*19.052=24mm
The insulation between HV and LV winding is 24 mm thick 0.8mm thick paper insulated LV winding, 8mm is left of oil duct and again 8mm insulation is warped.
∴ Inside diameter of HV winding, DHVI=DLVO+2*thickness of insulation
=240.2+2*24 mm
=288.2mm
∴Outside diameter of HV winding,DHVO= DHVI+2*bp
=288.2+2*19
=326.2mm
Clearance between winding=333.321-326.2=7.121 mm
Resistance:
Mean diameter of primary=(288.2+326.2)/2=307.2
∴ Length of mean turns of primary L_mtp=π*307.2
=0.965m
Let ρ =0.021Ω〖mm〗^2/m
∴Resistance of primary r_p=(ρ*l)/A=(ρ*L_mtp*T_p)/A_p
∴r_p=(0.021*0.965*3464)/1.22=57.53 Ω
Now,
Mean diameter of secondary =(240.2+195.2)/2=217.7 mm
∴Length of mean turn of secondary L_mts=π*217.7
=0.683m
∴r_(s=) (0.021*0.683*2000)/2.01=14.27Ω
Hence,
∴Resistance referred to primary =r_p+(〖3464/2000)〗^2 r_s = 100Ω
∴ P.U. resistance of transformer =〖I_p R〗_p/V_p =(2.624*100)/19052=0.013
P.U
Leakage Reactance:
Mean diameter of winding = (326.2+195.2)/2=260.7mm
∴Length of mean turns,L_mt=π*250.75= 0.819 m
Height of winding L_c=L_(cs+L_cp )/2=(471+395)/2=0.433 mm
∴ Leakage reactance of transformer referred to primary side,
〖 X〗_p =2*π*f*μ_0*〖T_p〗^2*L_mt/lc(a+b_(p+b_s )/3)*〖10〗^(-3)
Where,
a=24 mm
〖 b〗_p= 19 mm
bs= 22.25 mm
∴X_p =2*π*50*μ_0*〖2142〗^2*0.788/0.358(15+(20.85+12.1)/3)*〖10〗^(-3) = 338.24 Ω
∴ P.U leakage reactance E_x=〖I_p x〗_p/V_p =(2.624*338.24)/19052=0.046 P.U
∴ P.U. impedance =√(〖E_x〗^2+〖E_r〗^2 ) =0.048 P.U.
Regulation:
∴P.U. regulation ε=E_x sinϕ +E_r cosϕ
s.n
|
|
ε
|
||
1.
|
1
|
0.013
|
||
2.
|
0
|
0.046
|
||
3.
|
0.8(lag)
|
0.038
|
Losses:
1)〖 I〗^2R loss〖(P〗_c):
At 〖75〗^oC,
∴I^2R loss = 3〖I_p〗^2 R_p=3*〖2.624〗^(2*) 100=2065.6watt
Taking stray load loss 15% of above,
∴Total I^2R loss (P_c)=1.15*2065.6=2375.45 watt
2) Core loss =P_i
Let, density of lamination be 〖7.6*10〗^3 〖kg/m〗^3
We use the grade 92 HRS so, from loss curve of Electrical transformer steel at B_m=1.2 Wb/m^2(for limb), specific iron loss=1.8watt/Kg
Also,
Weight of limb=3*H_w*A_i*〖7.6*10〗^3
=3*0.487*0.0206〖*7.6*10〗^3
=228.73 kg
∴Limb loss =1.8*228.73=411.72 watt
Weight of two yoke =2*W*A_w 〖*7.6*10〗^3
=2*0.911*0.079*7.6*1000
=1093.92 kg
Corresponding to flux density 1 Wb/m^2 specific core loss is 1.2watt/kg
∴core loss in yoke =1.2*1093.92
=1312.71 watt
Hence,
∴Total core loss=411.72+1312.71 =1724.43 watt
Efficiency:
∴ɳ at full load and unity power factor =(output power)/(input power)*100%
=150000/(150000+1724.43+2375.45)*100% =97.39%
For maximum efficiency , x2Pc=Pi
∴x=0.85
Thus, the maximum efficiency occurs at 85% of full load.
No load current:
Flux density of core= 1.2Wb/mm2
Flux density of yoke=1.0Wb/ mm2
From B-H curve for electrical transformer steel grade 92, atc=400A/m and aty=120A/m
∴Total magnetizing mmf=3*400*0.487+2*120*0.9117=1419.3 AT
Now,
∴Magnetizing mmf per phase,AT0=1419.3/3=473.1 AT
∴Magnetizing current,Im=AT0/(√2 Tp)=0.0966A
∴Loss component of no load current ,IL= core loss/3vp=1724.43/57156=0.03A
∴No load current I0=0.101A
Hence,
∴No load current as percentage of full load current =0.101/2.624*100%
=3.85%
Tank:
Height of frame, H=823.76mmso,
now allowing 150mm for base and 250mm for oil .
Height of oil level=0.8237+0.15+0.25=1.22m
Allowing 250 mm for lead,
Hence, height of tank,Ht=1.061+0.25=1.47m
Assuming clearance of 50 mm on each side,
Width of tank=2D+DHVO+2*50 mm
=2*0.3333+0.326+0.1
=1.086 m
Assuming,50mm clearance on both sides
∴length of tank,Lt=DHVO+2*50 mm =0.326+0.1 =0.426 m
Tubes:
Total loss dissipating surface of tank,St=2*(1.086+0.426)
=3.024 m2
Total specific loss due to radiation and convection is 12.5 w/m2-°c
Temperature rise =(2375.45+1724.4)/(12.5*3.024)
=108.42 °c
Since temperature rise exceed the maximum limitation given i.e 40 °c,so plain tank is not sufficient for cooling and tubes are required.
Heat dissipation by plain tank = 12.5 w/°c
Heat dissipation by tubes by convection =6.5*1.4*xst = 9.1 xst
Total heat dissipation = st (12.5+9.1x)
Total area of tank wall and tubes =st(1+x)
xst = 1/9.1 [(total loss)/θ - 12.5st ] = 7.1095 m2
Area of each tubes = π *dt *lt = 0.19 m2
Where dt = diameter of tubes =50 mm
lt = length of tubes = 1.25 m
Numbers of tubes = (Area of tubes)/(Area of each tubes) = 7.1095/0.19 = 36 each spaced at 75 mm
Design sheet
KVA 150 phase 3 frequency 50 Hz Star/delta
Line voltage
h.v. 33000 v phase voltage h.v
19052 v
l.v.11000 v l.v.11000 v
Line
current h.v. 2.624A phase current h.v 2.624A
l.v. 7.86 A l.v. 4.54 A
Type –
Core
Type of cooling – ON
Core
1
|
Materials
|
|
0.35 mm thick 92 grade
|
2
|
Output constant
|
K
|
0.45
|
3
|
Voltage per turn
|
Et
|
5.5v
|
4
|
Circumscribing circle diameter
|
d
|
192.2 mm
|
5
|
Number of steps
|
|
2
|
6
|
Dimensions
|
|
|
|
|
a
|
163.37 mm
|
|
|
b
|
101.87mm
|
7
|
Net iron area
|
Ai
|
20.6*103 mm
|
8
|
Flux density
|
Bm
|
1.2Wb/m2
|
9
|
Flux
|
![]() |
0.02472 Wb
|
10
|
Weight
|
|
228.73Kg
|
11
|
Specific iron loss
|
|
1.8Watt/Kg
|
12
|
Iron loss
|
|
411.72Watt
|
Yoke
1
|
Depth of yoke
|
Dy
|
163.37mm
|
2
|
Height of yoke
|
Hy
|
168.13mm
|
3
|
Net yoke area
|
|
24.72*103 mm2
|
4
|
Flux density
|
|
1 Wb/m2
|
5
|
Flux
|
|
0.02472 Wb
|
6
|
weight
|
|
1093.92 Kg
|
7
|
Specific iron loss
|
|
1.2 Watt/Kg
|
8
|
Iron loss
|
|
1372.71 Watt
|
Windows
1
|
Number
|
|
2
|
2
|
Window space factor
|
Kw
|
0.2
|
3
|
Height of window
|
Hw
|
487.5mm
|
4
|
Width of window
|
Ww
|
160.5 mm
|
5
|
Window area
|
Aw
|
79.22*103 mm2
|
Frame
1
|
Distance between adjacent limbs
|
D
|
333.32 mm
|
2
|
Height of frame
|
H
|
823.76 mm
|
3
|
Width of frame
|
W
|
911.17 mm
|
4
|
Depth of frame
|
Dy
|
163.37 mm
|
S.N
|
Windings
|
L.v
|
H.v
|
1
|
Type of winding
|
Cross over
|
Cross over
|
2
|
connection
|
delta
|
star
|
3
|
Conductor
|
|
|
|
Dimension- Bare
|
1.6 mm
|
1.25 mm
|
|
Insulated
|
1.775 mm
|
1.45 mm
|
|
Area
|
2.01mm2
|
1.22 mm2
|
|
Number in parallel
|
None
|
None
|
4
|
Current density
|
2.26A/mm2
|
2.13 A/mm2
|
5
|
Turns per phase
|
2000
|
3464
|
6
|
Coils total number
|
24
|
39
|
|
Per core leg
|
8
|
13
|
7
|
Turns per coil
|
250
|
12of 250, 1 of 464 turns
|
|
per layers
|
25
|
25
|
8
|
Number of layers
|
10
|
10
|
9
|
Height of winding
|
395mm
|
471 mm
|
10
|
Depth of winding
|
22.25mm
|
19 mm
|
11
|
Insulation between layers
|
1.5 mm pressboard
|
0.8 mm
|
|
Between coils
|
5.0 mm spacers
|
3.0 mm spacers
|
12
|
Coils diameters inside
|
195.2 mm
|
288.2 mm
|
|
outside
|
240.2mm
|
326.2 mm
|
13
|
Length of mean turn
|
0.683 m
|
0.965 m
|
14
|
Resistance at 75°c
|
14.27
![]() |
57.53
![]() |
Insulation
1
|
Between l.v. winding and core
|
Press board wraps 1.5 mm
|
2
|
Between l.v. winding and h.v. winding
|
Bakelized paper 8.0 mm
|
3
|
Width of duct between l.v. and h.v.
|
8 mm
|
Tank
1
|
Dimensions:height
|
Ht
|
1.47 m
|
|
Length
|
Lt
|
0.426 m
|
|
Width
|
Wt
|
1.086 m
|
2
|
Oil level
|
|
1.221m
|
3
|
Tubes
|
|
7.1095m2, 36 tubes each of
area 0.19 m2
|
4
|
Temperature rise
|
|
40°C
|
Impedance
1
|
p.u resistance
|
0.013 p.u
|
2
|
p.u reactance
|
0.046 p.u
|
3
|
p.u impedance
|
0.048 p.u
|
Losses
1
|
Total core loss
|
1724.43watt
|
2
|
Total copper loss
|
2375.45 watt
|
3
|
Total losses at full load
|
4099.88 watt
|
4
|
Efficiency at full load and unity p.f
|
97.39%
|
Very good keep it up
ReplyDeleteधन्यवाद सन्दिप सर।
ReplyDeleteWhat is arranged for numbers of turn of Winding with radially and axially?
ReplyDeleteHow can we divided for layer of transformer turns?
ReplyDeleteI want to know the ways for 5MVA, 66/11kV transformer design calculation
ReplyDelete